Part Number Hot Search : 
MK42G PCA9674 5962F 87C196 0EBU0 EMD38 SCC100A MS3102
Product Description
Full Text Search
 

To Download 6282-8110 Datasheet File

  If you can't view the Datasheet, Please click here to try to view without PDF Reader .  
 
 


  Datasheet File OCR Text:
  67 - a range of power relays with high insulation between circuits (2500 v) and 2 or 3 co or no contacts - pcb mount, plug-in faston 187 (4.8 x 0.5 mm) or faston 250 (6.3 x 0.8 mm) versions available - ac or dc coils - dual-function test button - module facilities: low consumption led indicator and surge supression diode available - rear din rail mount options - sockets and accessories: see 92 series - approvals (according to type): imq, semko, sev, cul, vde 3 62 power relays 16 - 20 a electric motor loads lifts door, gate openers plastic molding machines ceramics industry machines escalators series
38 7.9 7.9 11.1 11.1 8.6 35.5 45.5 6 7.6 8 11.2 38 7.9 7.9 22.2 68 62.22 62.23 62.22 62.23 7 a 9 b 1 4 3 6 7 89 ab 1 4 3 6 2 5 62.22 62.23 p.c.b. relay type 62.22 2 co (dpdt) 16 a type 62.23 3 co (3pdt) 16 a (*) - tin plated copper pins (1.5 x 0.8 mm) - standard contact material: ag cdo - options: see coding table page 76 - ordering information: see page 76 (*) common phase connection; if different phases are connected to adjacent contacts, then rated current = 10 a 250 v ac (p max = 2500 v a) 62.22 - 0300 62.23 - 0300 4 6 ab 11.2 8 7.6 8.7 7.9 22.2 7.9 79 2 4 6 ab 11.2 8 7.6 8.7 7.9 11.1 7.9 79 2 5 8 11.1 62.22 - 0300 62.23 - 0300 p.c.b. relay (3 mm gap between open contacts) type 62.22 - 0300 2 no (dpst) 20 a type 62.23 - 0300 3 no (3pst) 16 a (*) - tin plated copper pins (1.5 x 0.8 mm) - standard contact material: ag cdo - options: see coding table page 76 - ordering information: see page 76 (*) common phase connection; if different phases are connected to adjacent contacts, then rated current = 10 a 250 v ac (p max = 2500 v a) c c 62.22 - 0300 7 a 9 b 4 6 62.23 - 0300 7 89 ab 5 4 6 62.22 4 6 ab 5.8 8 7.6 8.7 7.9 22.2 7.9 1 3 7 9 5.4 2 4 6 ab 5.8 8 7.6 8.7 7.9 11.1 7.9 13 79 5.4 2 5 2 8 11.1 8.6 35.5 45.5 6 7.6 8 5.8 5.5 38 7.9 7.9 11.1 11.1 38 7.9 7.9 22.2 62.23 0300
69 62.32 62.33 62.43 b 7.9 a 7.9 22.2 35.5 1.5 5.5 8.3 7.6 8.6 3 6 9 1 4 7 b 7.9 a 7.9 11.1 35.5 1.5 5.5 8.3 7.6 8.6 3 6 9 1 4 7 2 5 8 11.1 62.42 7 a 9 b 1 4 3 6 7 89 ab 1 4 3 6 2 5 7 a 9 b 1 4 3 6 7 89 ab 1 4 3 6 2 5 38 22 8 8 38 11.1 8 8 8.6 35.5 45.5 7 7.6 8.3 5.5 38 22 7.9 7.9 8.6 35.5 45.5 7 7.6 8.3 5.5 38 11.1 7.9 7.9 62.32 62.33 62.42 62.43 62.43 62.42 p.c.b. relay type 62.42 2 co (dpdt) 16 a type 62.43 3 co (3pdt) 16 a (*) - tin plated copper pins (1.5 x 0.5 mm) - test button, led and diode available - standard contact material: ag cdo - option: see coding table page 76 - ordering information: see page 76 (*) common phase connection; if different phases are connected to adjacent contacts, then rated current = 10 a 250 v ac (p max = 2500 v a) faston 187 plug-in relay type 62.32 2 co (dpdt) 16 a type 62.33 3 co (3pdt) 16 a (*) - tin plated copper connections: faston 187 (4.8 x 0.5 mm) - test button, led and diode available - standard contact material: ag cdo - options: see coding table page 76 - ordering information: see page 76 (*) common phase connection; if different phases are connected to adjacent contacts, then rated current = 10 a 250 v ac (p max = 2500 v a) c c 62.32 62.43
38 5.6 5.6 4.6 17.6 4.6 8.6 35.5 45.5 6 7.6 8 11.3 38 5.6 6.5 6.5 5.6 4.6 4.6 4.6 38 5.6 5.6 4.6 17.6 4.6 38 5.6 6.5 6.5 5.6 4.6 4.6 4.6 70 62.52 - 0300 62.52 62.52 - 0300 62.53 - 0300 62.53 - 0300 62.52 62.53 62.53 8.6 35.5 45.5 6 7.6 8 5.8 5.5 7 a 9 b 1 4 3 6 7 89 ab 1 4 3 6 2 5 4 56 ab 5.8 8 7.6 8.7 5.6 5.6 4.6 4.6 4.6 6.5 6.5 1 23 7 89 5.4 2 4 6 ab 5.8 8 7.6 8.7 5.6 5.6 4.6 17.6 4.6 1 3 7 9 5.4 2 4 56 ab 8 7.6 8.7 5.6 5.6 4.6 4.6 4.6 6.5 6.5 7 89 2 11.3 2 4 6 ab 11.3 8 7.6 8.7 5.6 5.6 4.6 17.6 4.6 7 9 7 a 9 b 4 6 7 89 ab 4 6 5 62.52 62.53 62.52 - 0300 62.53 - 0300 p.c.b. relay with bifurcated terminals type 62.52 2 co (dpdt) 16 a type 62.53 3 co (3pdt) 16 a (*) - tin plated copper pins (1.7 x 0.8 mm) - standard contact material: ag cdo - options: see coding table page 76 - ordering information: see page 76 (*) common phase connection; if different phases are connected to adjacent contacts, then rated current = 10 a 250 v ac (p max = 2500 v a) p.c.b. relay with bifurcated terminals (3 mm gap between open contacts) type 62.52 - 0300 2 no (dpst) 20 a type 62.53 - 0300 3 no (3pst) 16 a (*) - tin plated copper connections (1.7 x0.8 mm) - standard contact material: ag cdo - options: see coding table page 76 - ordering information: see page 76 (*) common phase connection; if different phases are connected to adjacent contacts, then rated current = 10 a 250 v ac (p max = 2500 v a) c c 62.52 62.53 0300
8.6 35.5 45.5 7 7.6 8.3 5.5 8.6 35.5 45.5 8 7.6 8 5.5 5.8 71 20.1 3.6 3.5 12.2 45 9.5 3.5 63.2 3.6 38 20.1 3.6 3.5 12.2 45 9.5 3.5 63.2 3.6 38 62.63 62.62 7 a 9 b 1 4 3 6 7 89 ab 1 4 3 6 2 5 62.83 62.82 7 a 9 b 1 4 3 6 7 89 ab 1 4 3 6 2 5 62.82 62.83 38 22.2 7.9 7.9 38 11.1 7.9 7.9 62.62 62.63 38 22.2 7.9 7.9 38 11.1 7.9 7.9 faston 250 flange relay type 62.82 2 co (dpdt) 16 a type 62.83 3 co (3pdt) 16 a (*) - cover with flanges for 3 ? 3.5 mm screw mount - tin plated copper connections: faston 250 (6.3 x 0.8 mm) - test button, led and diode available - standard contact material: ag cdo - options: see coding table page 76 - ordering information: see page 76 (*) common phase connection; if different phases are connected to adjacent contacts, then rated current = 10 a 250 v ac (p max = 2500 v a) faston 187 flange relay type 62.62 2 co (dpdt) 16 a type 62.63 3 co (3pdt) 16 a (*) - cover with flanges for 3 ? 3.5 mm screw mount - tin plated copper connections: faston 187 (4.8 x 0.5 mm) - test button, led and diode available - standard contact material: ag cdo - options: see coding table page 76 - ordering information: see page 76 (*) common phase connection; if different phases are connected to adjacent contacts, then rated current = 10 a 250 v ac (p max = 2500 v a) c c 62.62 62.83
between coil and contacts between open contacts between open contacts no version between adjacent contacts between frame and live parts 72 2500 v 1500 v 2500 v 2500 v 4000 v 3 20 ?10 3 m w c 400 36000 cycles/h 600 cycles/h ?40 to + 70 c (t max = 50 c no version) ac: 10 ?10 6 cycles dc: 30 ?10 6 cycles ip 40 30 ms (including contact bounce) 30 ms (including contact bounce) continuous c (according to iec 255) all - or - nothing 2 technical data dielectric strength tested at: leakage current 10 ma for 1 min at 50 hz 62.82 - 0300 62.83 - 0300 38 22.2 7.9 7.9 38 11.1 7.9 7.9 62.82 - 0300 62.83 - 0300 20.1 3.6 3.5 12.2 45 9.5 3.5 63.2 3.6 38 7 a 9 b 4 6 7 89 ab 4 6 5 faston 250 flange relay (3 mm gap between open contact) type 62.82 - 0300 2 no (dpst) 20 a type 62.83 - 0300 3 no (3pst) 16 a (*) - cover with flanges for 3 ? 3.5 mm screw mount - tin plated copper connections: faston 250 (6.3 x 0.8 mm) - test button, led and diode available - standard contact material: ag cdo - options: see coding table page 76 - ordering information: see page 76 (*) common phase connection; if different phases are connected to adjacent contacts, then rated current = 10 a 250 v ac (p max = 2500 v a) c surge test (1.2/50 m s) voltage between coil and contacts insulation resistance insulation group max switching frequency - without load: - at rated load: ambient temperature mechanical life protection category of enclosures operate and release time pick-up time (from 0 to u n ) drop-out time (from u n to 0) type of duty pick-up class dielectric test type of relay relay without external ground 8.6 35.5 45.5 8 7.6 8 11.3 62.82 0300
73 k 62 reduction factor 1 0.8 0.6 0.4 1 0.4 0.6 0.8 0.2 cos j k load reduction factor vs cos j . contact specification nominal rate in ac1 rated current maximum peak current rated voltage maximum switching voltage breaking capacity in dc1 single phase hp motor rating contact resistance: - initial standard contact material 2 - 3 co (dpdt - 3pdt) 3 no (3pst) 4000 va 16 a 30 a 250 v ac 400 v ac 0.8 kw, 1.2 hp 50 m w ag cdo 62.22 - 0300 62.52 - 0300 62.82 - 0300 5000 va 20 a 40 a 250 v ac 400 v ac 0.8 kw, 1.2 hp 50 m w ag cdo see diagram h 62 breaking capacity for dc1 load at 600 cycles/h. load applied to 1 contact. a = for relays types 62.22 - 0300 - 62.52 - 0300 and 62.82 - 0300 b = other types h 62 f 62 13 4 kva 5 ?10 6 2 0 load cycles 5 ?10 5 5 ?10 4 20 60 100 140 180 220 20 10 6 4 2 1 0.6 0.4 0.2 0.1 voltage v (dc) a b contact life vs ac1 load at 600 cycles/h. max switching current (a)
74 coil specification ac 2.2 va 0.8 ? 1.1 u n 0.8 u n 3 0.2 u n 180 a f (+155 c) 41 c/w dc 1.3 w 0.8 ? 1.1 u n 0.6 u n 3 0.1 u n 250 a f (+155 c) 41 c/w ac - no 3 va 0.85 ? 1.1 u n 0.8 u n 3 0.2 u n 220 a f (+155 c) 38 c/w dc - no 3 w 0.85 ? 1.1 u n 0.6 u n 3 0.1 u n 420 a f (+155 c) 38 c/w versions: ac - alternating current 50/60 hz dc - direct current di - dc coil with a diode in parallel rated power operating range holding voltage must drop-out voltage nominal magnetomotive force thermal insulation class of wire thermal resistance conducted disturbance immunity burst (acc. to en 61000-4-4) livel 4 (4kv) surge (acc. to en 61000-4-5) livel 4 (4kv) 6 12 24 48 60 110 125 230 240 co 4.8 9.6 19.2 38.4 48 88 100 184 192 no 5.1 10.2 20.4 40.8 51 93.5 106 196 204 u min (v) co 6.6 13.2 26.4 52.8 66 121 137 253 264 u max (v) no 6.6 13.2 26.4 52.8 66 121 137 253 264 co 4.6 19 80 320 500 1800 2000 7250 8500 resistance r ( w ) no 3.5 14 67 220 350 1200 1400 5000 5300 co 367 183 92 46 37 20 17.6 10.4 9.2 nominal absorption i at u n 50 hz (ma) no 550 275 137 70 55 30 26 14 13.2 co 0.05 0.2 0.8 3.2 4.9 16.5 22 66 78 no 0.032 0.13 0.52 2 3.3 11 14.6 50 55 rated voltage u n (v) ac version data (r values relate to +20 c. tolerance of r and i values: 10%.) inductance with closed armature (h) 6 12 24 48 60 110 125 rated voltage u n (v) co 4.8 9.6 19.2 38.4 48 88 100 no 5.1 10.2 20.4 40.8 51 93.5 106 u min (v) co 6.6 13.2 26.4 52.8 66 121 137 u max (v) no 6.6 13.2 26.4 52.8 66 121 137 co 28 110 445 1770 2760 9420 12000 resistance r ( w ) no 12 48 192 770 1200 4000 5200 co 214 109 54 27 21.7 11.7 10.4 nominal absorption i at u n (ma) no 500 250 125 63 50 27 24 dc version data (r values relate to +20 c. tolerance of r and i values: 10%.)
75 s 62no/1 10 20 30 40 50 60 0 10 20 30 40 50 70 60 min 1.1 u n u n 0.85 u n 80 90 s 62no/2 10 20 30 40 50 60 0 10 20 30 40 50 70 60 min 1.1 u n u n 0.85 u n 80 90 temperature rise " d t " vs applied voltage. dc coils, no version. temperature rise " d t " vs applied voltage. ac 50 hz coils, no version. heating time temperature rise " d t " ( c) heating time temperature rise " d t " ( c) s 62/1 s 62/2 10 20 30 40 50 60 0 10 20 30 40 50 70 60 min 10 20 30 40 50 60 0 10 20 30 40 50 70 60 min 1.1 u n u n 0.8 u n 1.1 u n u n 0.8 u n temperature rise " d t " vs applied voltage. dc coils. heating time temperature rise " d t " ( c) temperature rise " d t " vs applied voltage. ac 50 hz coils. heating time temperature rise " d t " ( c) coil specification dc coil min pick-up voltage vs ambient temperature. valid for co (dpdt) types. umin = pick-voltage u n = rated voltage r 62 1 0.9 -20 0 20 40 60 80 umin u n ambient temperature ( c) 0.8 0.7 0.6 0.5 - 40
76 coil types direct current alternating current at 50/60 hz direct current with a diode in parallel to coil coil versions dc ac di code 9 8 3 ordering information 6 282 8 0330 230 series type no. of poles (co) coil version (see table) coil rated voltage ab c d option (see table) example: a 62 series faston 250 connection relay with 2 co (dpdt) rated at 230 v ac with no contacts and led has the following code: for standard relays with no options, use the first 8 digits only. standard 0 standard no a contact material b 0 3 circuit contact c d additional features special applications standard top mount flange top din rail mount rear din rail mount 0 5 7 8 options (* available for dc coil only) standard test button led (ac) test button + led, ac only led + diode (positive to a) dc only test button + led + diode (positive to a) dc only led + diode (positive to b) dc only test button + led + diode (positive to b) dc only 0 1 3 5 *6 *7 *8 *9 test button (0010) led (0030) rear din 46277 rail mount (0008) coil version = 3 a option= 0030 option= 0060 - 0070 option= 0080 - 0090 babbaba
77 92 - a range of sockets and accessories for the 62 series relays - solder, screw terminal, pcb, panel or din rail 46277 mount versions available - ip 20 finger protection with additional plastic cover - flammability in accordance with ul 94 - approvals (according to type): sev, cul sockets & accessories for 62 series relays series
screw terminal socket (panel or din rail 46277 mount) type 92.43.1 for relays types 62.32 - 62.33 accessories: retaining clip type 092.53 accessories: ip 20 protective cover type 092.55 characteristics - load: 16 a 250 v - insulation resistance: 3 10 3 m w - dielectric strength: 3 2.5 kv ac - body material: self-extinguishing ppem (v1) - connections: cu zn 33 nickel plated - non removable pozidrive slotted terminal screws. 78 92.13 92.33 = 11 35.5 26.5 = 24 81.5 35 23 18.5 10.5 1 36 138 40 1.6 5.5 8.3 7.6 11.1 11.1 4.5 9 3.75 1.6 3.75 50 13.1 5.5 8.3 7.6 15.5 40 9.5 11.1 11.1 8.3 9 1 50 138 11 4.5 31 42.5 = = 35.5 11 21 13 c 92.13 92.43.1 p.c.b. socket (flange mount with m3 screws) type 92.13 for relays types 62.32 - 62.33 accessories: retaining clip type 092.54 solder connections socket type 92.33 for relays types 62.32 - 62.33 accessories: retaining clip type 092.54 characteristics - load: 32 a 250 v (10 a max for each contact circuit) - insulation resistance: 3 10 3 m w - dielectric strength: 3 2.5 kv ac - body material: self-extinguishing ppem (v1) - connections: cu zn 33 tin plated c


▲Up To Search▲   

 